Veeder Root / Tank Monitor Integration Quick-Start Guide

Step-by-step guide for integrating Veeder Root ATG (Automatic Tank Gauging) systems with BACnet, Modbus, or EtherNet/IP via a QuickServer gateway.

Overview

Veeder Root (by Gilbarco) manufactures Automatic Tank Gauging (ATG) systems — the TLS-3XX series — used in fuel storage monitoring, gas stations, and industrial tank farms. These systems track tank levels, temperatures, and leak detection status via a proprietary serial protocol.

Integrating a Veeder Root panel into a building management system (BMS) or SCADA platform requires a protocol gateway to translate the ATG data into BACnet, Modbus, or EtherNet/IP. A QuickServer handles this conversion.

This guide walks through the intake, wiring, configuration, and commissioning steps for a Veeder Root integration project.

Veeder Root ATG Integration Architecture

Before You Start

Collect this information before ordering hardware or starting configuration. Veeder Root projects have a high rate of delays due to missing intake information — gathering these details upfront avoids weeks of back-and-forth.

TLS Controller Model

Identify the Veeder Root controller model:

  • TLS-350 — Most common, serial interface
  • TLS-300 — Older model, serial interface
  • TLS-450 / TLS-450 Plus — Newer model, may support TCP/IP in addition to serial

The model determines the protocol variant and driver configuration on the QuickServer.

Number of Tanks

Count the total number of tanks connected to the ATG panel. This determines:

  • How many BACnet objects or Modbus registers the gateway will expose
  • Whether the gateway’s point tier (250 / 500 / 1000) is sufficient
  • The data points per tank: typically level, volume, temperature, water level, and alarm status

[!TIP] Ask for a System Setup Printout from the Veeder Root panel — this lists all connected tanks, sensor types, and tank dimensions. It’s the most reliable source of tank count and configuration.

Connection Type and Serial Settings

Standard Veeder Root serial settings:

ParameterDefault Value
InterfaceRS-232
Baud Rate9600
Data Bits8
ParityNone
Stop Bits1

Confirm these match the actual panel settings — non-default baud rates are rare but possible on newer TLS-450 systems.

Target Protocol

Which protocol does the BMS or SCADA system expect?

Target ProtocolCommon Use Case
BACnet/IPBuilding management systems (Tridium, Siemens, Johnson Controls)
Modbus TCPSCADA systems, industrial monitoring
EtherNet/IPAllen-Bradley PLC integration

Existing Gateway (If Replacement)

If replacing an existing Chipkin gateway (e.g., CAS-2700-02B → QuickServer):

  • Request the existing config file (config.csv) — this preserves point mappings
  • Record the current BACnet Device Instance — preserve it on the new gateway to avoid BMS-side reconfiguration
  • Note the serial wiring — the RS-232 pinout may differ between the old and new gateway

[!WARNING] Old CAS-2700-02B configuration files are not directly compatible with QuickServer. The config will need to be rebuilt, but the existing file provides the point list and Device Instance as a reference.

Step 1: Wire the Serial Connection

Connect the Veeder Root panel to the QuickServer serial port via RS-232.

Typical wiring (DB-9):

QuickServer PinVeeder Root PinSignal
Pin 2 (RX)Pin 3 (TX)Data from panel to gateway
Pin 3 (TX)Pin 2 (RX)Data from gateway to panel
Pin 5 (GND)Pin 5 (GND)Signal ground

[!NOTE] RS-232 is a point-to-point connection — only one gateway per serial port on the Veeder Root panel. For multi-panel installations, each panel requires its own serial port or a serial-to-TCP converter.

Step 2: Configure the QuickServer

  1. Connect to the QuickServer web interface — browse to the gateway’s IP address
  2. Load the Veeder Root driver — select Veeder Root ATG as the source protocol
  3. Set serial parameters — 9600 / 8 / N / 1 (confirm against actual panel settings)
  4. Configure tank count — enter the number of tanks connected to the panel
  5. Map data points — each tank exposes:
    • Tank Level (volume in gallons or liters)
    • Product Temperature
    • Water Level
    • Tank Ullage (remaining capacity)
    • Alarm Status (leak detection, overfill, low level)

For help with the QuickServer web interface, see the firmware update guide for general navigation concepts, or contact Chipkin support for configuration assistance.

Step 3: Configure the Target Protocol

BACnet/IP Target

  • Set the Device Instance — unique on the BACnet network (if replacing a CAS-2700-02B, use the same Device Instance)
  • Configure BACnet objects — each tank data point maps to a BACnet Analog Input (AI) or Analog Value (AV) object
  • Set the IP address and subnet — must be on the same subnet as the BMS, or configure BBMD for cross-subnet discovery

Modbus TCP Target

  • Set the Slave/Unit ID — must be unique on the Modbus network
  • Map tank data to Holding Registers — see the Modbus addressing reference for register numbering conventions
  • Confirm data types with the SCADA vendor — most tank values are 32-bit floats. See the data types reference.

EtherNet/IP Target

  • Generate an EDS file from the QuickServer web interface — the PLC programmer needs this
  • Confirm DATA_TABLE_WRITE if any setpoints or commands are needed. See the EtherNet/IP integration guide.

Step 4: Commission and Verify

  1. Power on the Veeder Root panel and QuickServer
  2. Check serial communication — the QuickServer web interface shows connection status and incoming data
  3. Verify tank data — compare values on the QuickServer’s diagnostic page against the Veeder Root panel display
  4. Test BMS discovery — run a device scan from the BMS or use CAS BACnet Explorer for BACnet installations
  5. Verify all tanks appear — for multi-tank systems, the BMS may need a full re-scan to discover all tank objects

[!WARNING] On multi-tank systems (10+ tanks), the BMS may initially show only Tank 1 data. This is typically a BMS-side discovery issue, not a gateway problem. Re-scan the BACnet network from the BMS to discover all tank objects.

Common Failures

SymptomLikely CauseFix
No serial dataWiring TX/RX swapped, or wrong baud rateCheck RS-232 pinout and serial settings
Gateway connects but shows zerosWrong tank count in config, or panel not reportingVerify panel System Setup Printout, check tank sensor connections
BMS sees gateway but no tank objectsPoint count exceeds QuickServer tierUpgrade point tier (250 → 500 → 1000)
BMS sees Tank 1 onlyBMS needs re-scan after config changePerform full BACnet device re-scan from BMS
Replacing CAS-2700-02B — BMS lost all pointsDevice Instance changedSet new gateway’s Device Instance to match old CAS-2700-02B
Data values look wrong (negative or overflow)Data type mismatch on target sideConfirm 32-bit float vs integer mapping with BMS vendor

Chipkin Tools

  • QuickServer — Multi-protocol gateway with Veeder Root ATG driver support
  • CAS BACnet Explorer — Verify BACnet device discovery and object mapping after commissioning
  • CAS Modbus Scanner — Verify Modbus register mapping for Modbus TCP targets
  • Chipkin Support — Configuration assistance, wiring diagrams, and commissioning support