Modbus Data Types & Byte Order Reference

How to handle 32-bit floats, byte order (endianness), multi-register values, and scaling factors in Modbus integrations. Includes a device byte-order lookup table.

Overview

After register addressing, byte order (endianness) is the second most common source of Modbus integration errors. When combining two 16-bit Modbus registers into a 32-bit float or integer value, the byte arrangement must match between the source device and the gateway. A mismatch produces garbled data — zeros, negative numbers, or nonsensical exponent values.

This article covers byte order conventions, data type handling, scaling factors, and a device-specific lookup table for common equipment.

Modbus Byte Order (Endianness) — 32-bit Float Example

Modbus Register Data Types

Every Modbus register is 16 bits (2 bytes). Larger values require combining multiple registers.

Single-Register Types (16-Bit)

These types fit in one register — no byte order concerns.

Data TypeRangeExample ValueTypical Use
UINT16 (unsigned integer)0 to 65,5354096 = fan speed RPMStatus codes, raw sensor counts, enumerated states
INT16 (signed integer)-32,768 to 32,767-120 = -12.0°C (with ÷10 scaling)Temperatures, pressures, bipolar analog signals
Boolean / Bit0 or 11 = alarm activeCoils and discrete inputs (FC01, FC02)

Multi-Register Types (32-Bit)

These require two registers — byte order is critical. See Byte Order below.

Data TypeRangeExample ValueTypical Use
UINT32 (unsigned 32-bit integer)0 to 4,294,967,2951,200,000 = energy kWh totalizerCounters, totalizers, accumulated runtime hours
INT32 (signed 32-bit integer)-2,147,483,648 to 2,147,483,647-500,000 = reverse power flow in wattsBidirectional power, differential pressure
Float32 (IEEE 754 single-precision)±1.18 × 10⁻³⁸ to ±3.40 × 10³⁸ (~7 significant digits)72.5 = temperature °F; 101.325 = pressure kPaMost analog values: temperature, humidity, voltage, current, power

[!NOTE] Float32 is the most common multi-register type in building automation. If a device datasheet lists analog values (temperatures, pressures, power), assume Float32 unless stated otherwise.

Float32 examples in practice:

Raw Hex (2 registers)Float32 ValueWhat It Represents
0x4291_000072.5Room temperature (°F)
0x42CA_0000101.0Barometric pressure (kPa)
0x447A_00001000.0Power consumption (W)
0x0000_00000.0Zero reading — or possibly wrong byte order
0xFF7F_FFFFNaNInvalid / sensor fault

Extended Types (64-Bit and Beyond)

These are rare in building automation but do appear on some devices.

Data TypeRegistersRangeTypical Use
Float64 (IEEE 754 double-precision)4±5.0 × 10⁻³²⁴ to ±1.8 × 10³⁰⁸ (~15 significant digits)High-precision scientific instruments, energy totalizers
48-bit integer30 to 281,474,976,710,655Flow meter totalization (see Multi-Register Values)

[!WARNING] Some device documentation uses “double” to mean two 16-bit registers (32-bit total), not IEEE 754 double-precision (64-bit). Always confirm whether “double” means 32-bit or 64-bit at project intake.

Byte Order (Endianness) for 32-Bit Values

When two 16-bit Modbus registers form a 32-bit value, four byte arrangements are possible. Given bytes a (MSB), b, c, d (LSB):

OrderNotationDescriptionCommon Names
ABCDBig-EndianHigh word first, high byte firstStandard, IBM, “normal”
CDABWord-SwapLow word first, high byte within each wordMid-Big, sw
BADCByte-SwapHigh word first, bytes reversed within each wordMid-Little, sb
DCBALittle-EndianEverything reversedIntel, “reversed”

ABCD (Big-Endian) is the most common convention, but enough devices use other orders that you should never assume — always verify.

How to Identify the Correct Byte Order

  1. Check the manufacturer datasheet for byte order or endianness specification
  2. Read a known value — if a temperature sensor reads 72°F on the display, read the raw registers and test each byte order until the converted value matches
  3. Test systematically — try ABCD first, then CDAB, BADC, DCBA. Most real devices use either ABCD or CDAB

[!TIP] If 32-bit float reads return zeros, negative numbers, or values like 1.73e-38, the byte order is almost certainly wrong. Try word-swap (CDAB) first — it’s the most common non-standard order. See the Modbus Troubleshooting Guide for a full diagnostic walkthrough.

QuickServer Byte Order Flags

When configuring a QuickServer gateway, use these format flags to control byte order conversion:

Configuration SyntaxByte OrderWhen to Use
2.i16-1.floatABCD (Big-Endian)Default; most devices
2.i16-1.float-swCDAB (Word-Swap)GE meters, many industrial devices
2.i16-1.float-sbBADC (Byte-Swap)Less common; test if sw doesn’t work
2.i16-1.float-sDCBA (Little-Endian)Rare; full reversal

Known Device Byte Orders

This table documents byte order requirements confirmed through real-world integrations:

ManufacturerDeviceProtocolByte OrderScalingNotes
GEEPM6000 Power MeterModbus RTUCDAB (word-swap)÷100Most common non-standard order
EatonForeseerModbus TCPABCD (Big-Endian)—Standard order
Thermo FisherAquaSensors AV38Modbus RTUWord-order reversal—IEEE754 float; verify with scanner
CORDEXCXC HP ControllersModbus TCPCDAB (word-swap)—Initially deployed as big-endian; corrected
SchneiderSE5000 Power MetersModbus RTUFloat32 (ABCD)—Dual memory arrays needed for multi-protocol
YorkQuantum Q4 ChillerModbus RTUStandard÷10Temperature values require scaling
MitsubishiFX5 PLCModbus TCPInteger only÷10No native float; pre-scaled integers

[!TIP] Don’t see your device? Use the systematic test method above. Once confirmed, document the result for future projects.

Scaling Factors

Some devices store values as scaled integers rather than floating-point numbers. The raw register value must be divided (or multiplied) by a scaling factor to get the real-world value:

PatternExampleDevices
÷10Raw 725 → 72.5°FYork Quantum Q4 chillers, Mitsubishi FX5 PLCs
÷100Raw 7250 → 72.50°FGE EPM6000 power meters
÷1000Raw 72500 → 72.500High-precision sensors

Always check the register map for scaling notes. If register values are consistently 10× or 100× the expected value, a scaling factor is likely missing from your configuration. For register addressing fundamentals, see Modbus Addressing & Register Reference.

Multi-Register Values (Beyond 32-Bit)

Most Modbus values use 1 or 2 registers. Occasionally, devices use 3 or more registers for a single data point:

48-Bit Integers (3 Registers)

Some flow meters use three 16-bit registers (MSW → LSW) for totalization counters. QuickServer gateways cannot natively combine 3 registers into a single value.

Workaround options:

  • Pass the three raw register values separately and combine them in the downstream system
  • Use a custom script or middleware to perform the combination

64-Bit Doubles (4 Registers)

Rare in building automation. If a device datasheet specifies 64-bit doubles, confirm with the manufacturer — many devices that claim “double” actually use 32-bit floats occupying 2 registers.

Troubleshooting

For detailed symptom-based diagnostics, see the Modbus Troubleshooting Guide. Quick reference for data type issues:

  • Data reads as zeros → byte order mismatch (try CDAB), register offset, or data type mismatch (reading integer as float)
  • Data reads as negative or exponent values → wrong byte order, signed-vs-unsigned confusion, or missing scaling factor
  • Correct on device display but wrong in BACnet → verify with a Modbus scanner first to isolate Modbus side vs. BACnet conversion

Configuration Intake Questions

Add these to your standard Modbus intake checklist to prevent byte-order rework:

#QuestionImpact
1What is the byte order for 32-bit values? (Big-endian, word-swap, byte-swap, little-endian, unknown)Prevents the #2 most common integration error
2Are there any known scaling factors? (÷10, ÷100, ÷1000)Prevents “data values are wrong” callbacks
3Do 32-bit values use floating-point or integer format?Prevents data type mismatch
4Does the manufacturer documentation specify register pair byte order?Gets definitive answer vs. trial-and-error

Chipkin Tools

  • QuickServer — Protocol gateway with built-in byte order conversion flags (-sw, -sb, -s)
  • QuickServer — Next-generation protocol conversion gateway
  • CAS Modbus Scanner — Read raw register values to verify byte order before building configurations
  • Chipkin support — Expert help with byte order diagnosis and configuration